| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions < V5.0.0 for CVE-2013-3633 and versions < V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.1.0). The implementation of SNMPv3 does not check the user credentials sufficiently. Therefore, an attacker is able to execute SNMP commands without correct credentials. |
| The Siemens Synco OZW Web Server devices OZW672.*, OZW772.*, and OZW775 with firmware before 4 have an unspecified default password, which makes it easier for remote attackers to obtain administrative access via a network session. |
| Cross-site scripting (XSS) vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to inject arbitrary web script or HTML via unspecified vectors, a different vulnerability than CVE-2011-4511. |
| Siemens SIMATIC S7-400 PN CPU devices with firmware 5.x allow remote attackers to cause a denial of service (defect-mode transition and service outage) via (1) malformed HTTP traffic or (2) malformed IP packets. |
| Siemens SIMATIC S7-400 PN CPU devices with firmware 6 before 6.0.3 allow remote attackers to cause a denial of service (defect-mode transition and service outage) via crafted ICMP packets. |
| Untrusted search path vulnerability in Siemens SIMATIC STEP7 before 5.5 SP1, as used in SIMATIC PCS7 7.1 SP3 and earlier and other products, allows local users to gain privileges via a Trojan horse DLL in a STEP7 project folder. |
| A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions < V5.0.0 for CVE-2013-3633 and versions < V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.1.0). The user privileges for the web interface are only enforced on client side and not properly verified on server side. Therefore, an attacker is able to execute privileged commands using an unprivileged account. |
| The SNMP implementation in Siemens RuggedCom ROS before 3.11, ROS 3.11 for RS950G, ROS 3.12 before 3.12.4, and ROS 4.0 for RSG2488 allows remote attackers to cause a denial of service (device outage) via crafted packets. |
| WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allows remote attackers to discover a username and password via crafted parameters to unspecified methods in ActiveX controls. |
| The HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime generates predictable authentication tokens for cookies, which makes it easier for remote attackers to bypass authentication via a crafted cookie. |
| SQL injection vulnerability in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allows remote attackers to execute arbitrary SQL commands via a crafted SOAP message. |
| Siemens SIMATIC WinCC OA before 3.12 P002 January allows remote attackers to cause a denial of service (monitoring-service outage) via malformed HTTP requests to port 4999. |
| The integrated web server in Siemens SIMATIC WinCC OA before 3.12 P002 January allows remote attackers to execute arbitrary code via crafted packets to TCP port 4999. |
| Siemens SIMATIC WinCC OA before 3.12 P002 January uses a weak hash algorithm for passwords, which makes it easier for remote attackers to obtain access via a brute-force attack. |
| Stack-based buffer overflow in the Profinet DCP protocol implementation on the Siemens Scalance S Security Module firewall S602 V2, S612 V2, and S613 V2 with firmware before 2.3.0.3 allows remote attackers to cause a denial of service (device outage) or possibly execute arbitrary code via a crafted DCP frame. |
| Siemens RuggedCom Rugged Operating System (ROS) before 3.12, ROX I OS through 1.14.5, ROX II OS through 2.3.0, and RuggedMax OS through 4.2.1.4621.22 use hardcoded private keys for SSL and SSH communication, which makes it easier for man-in-the-middle attackers to spoof servers and decrypt network traffic by leveraging the availability of these keys within ROS files at all customer installations. |
| Multiple cross-site scripting (XSS) vulnerabilities in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allow remote attackers to inject arbitrary web script or HTML via a (1) GET parameter, (2) POST parameter, or (3) Referer HTTP header. |
| Absolute path traversal vulnerability in the ALMListView.ALMListCtrl ActiveX control in almaxcx.dll in the graphical user interface in Siemens Automation License Manager (ALM) 2.0 through 5.1+SP1+Upd2 allows remote attackers to overwrite arbitrary files via the Save method. |
| Siemens SINAMICS S/G controllers with firmware before 4.6.11 do not require authentication for FTP and TELNET sessions, which allows remote attackers to bypass intended access restrictions via TCP traffic to port (1) 21 or (2) 23. |
| WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, stores sensitive information under the web root with insufficient access control, which allows remote attackers to read a (1) log file or (2) configuration file via a direct request. |