| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| The login implementation in the Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, has a hardcoded account, which makes it easier for remote attackers to obtain access via an unspecified request. |
| SQL injection vulnerability in the login screen in the Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, allows remote attackers to execute arbitrary SQL commands via unspecified vectors. |
| Buffer overflow in the DiagAgent web server in Siemens WinCC 7.0 SP3 through Update 2 allows remote attackers to cause a denial of service (agent outage) via crafted input. |
| AscoServer.exe in the server in Siemens SiPass integrated MP2.6 and earlier does not properly handle IOCP RPC messages received over an Ethernet network, which allows remote attackers to write data to any memory location and consequently execute arbitrary code via crafted messages, as demonstrated by an arbitrary pointer dereference attack or a buffer overflow attack. |
| Multiple directory traversal vulnerabilities in Siemens WinCC 7.0 SP3 before Update 2 allow remote authenticated users to read arbitrary files via a crafted parameter in a URL. |
| HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled, allows remote attackers to cause a denial of service (application crash) by sending crafted data over TCP. |
| The TELNET daemon in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not perform authentication, which makes it easier for remote attackers to obtain access via a TCP session. |
| Invensys Wonderware InTouch 2012 R2 and earlier and Siemens ProcessSuite use a weak encryption algorithm for data in Ps_security.ini, which makes it easier for local users to discover passwords by reading this file. |
| The client application in Siemens COMOS before 9.1 Update 458, 9.2 before 9.2.0.6.37, and 10.0 before 10.0.3.0.19 allows local users to gain privileges and bypass intended database-operation restrictions by leveraging COMOS project access. |
| Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allow user-assisted remote attackers to execute arbitrary code via a crafted project file, related to the HMI web server and runtime loader. |
| Siemens SINAMICS S/G controllers with firmware before 4.6.11 do not require authentication for FTP and TELNET sessions, which allows remote attackers to bypass intended access restrictions via TCP traffic to port (1) 21 or (2) 23. |
| The authentication implementation in the web server on Siemens SCALANCE X-200 switches with firmware before 5.0.0 does not use a sufficient source of entropy for generating values of random numbers, which makes it easier for remote attackers to hijack sessions by predicting a value. |
| Siemens Simatic WinCC and PCS 7 SCADA system uses a hard-coded password, which allows local users to access a back-end database and gain privileges, as demonstrated in the wild in July 2010 by the Stuxnet worm, a different vulnerability than CVE-2010-2568. |
| The HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime has an improperly selected default password for the administrator account, which makes it easier for remote attackers to obtain access via a brute-force approach involving many HTTP requests. |
| Open redirect vulnerability in Siemens WinCC (TIA Portal) 11 and 12 before 12 SP1 allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks by leveraging improper configuration of SIMATIC HMI panels by the WinCC product. |
| core/getLog.php on the Siemens Enterprise OpenScape Branch appliance and OpenScape Session Border Controller (SBC) before 2 R0.32.0, and 7 before 7 R1.7.0, allows remote attackers to obtain sensitive server and statistics information via unspecified vectors. |
| Directory traversal vulnerability in Siemens SIMATIC WinCC OA before 3.12 P002 January allows remote attackers to read arbitrary files via crafted packets to TCP port 4999. |
| Cross-site scripting (XSS) vulnerability in core/handleTw.php on the Siemens Enterprise OpenScape Branch appliance and OpenScape Session Border Controller (SBC) before 2 R0.32.0, and 7 before 7 R1.7.0, allows remote attackers to inject arbitrary web script or HTML via unspecified vectors. |
| Buffer overflow in the embedded web server on the Siemens Scalance X Industrial Ethernet switch X414-3E before 3.7.1, X308-2M before 3.7.2, X-300EEC before 3.7.2, XR-300 before 3.7.2, and X-300 before 3.7.2 allows remote attackers to cause a denial of service (device reboot) or possibly execute arbitrary code via a malformed URL. |
| An unspecified ActiveX control in ActBar.ocx in Siemens Tecnomatix FactoryLink 6.6.1 (aka 6.6 SP1), 7.5.217 (aka 7.5 SP2), and 8.0.2.54 allows remote attackers to create or overwrite arbitrary files via the save method. |